2. Align the combination HW1490 Support Bars and
Burglary Module PCB with the holes located in HW1492
Right Side Plate and the HW1491 Left Side Plate. Se-
cure using four thumbscrews (item #4) and four external
tooth star washers (item #5).
3. Orient the Burglary Module above the motherboard
with its terminals towards the left side. On the right side
of the Burglary Module is a polarized 12 pin female rib-
bon connector "J2"; insert J2 into the male 12 pin con-
nector "J8" on the motherboard. Using the four 6-32
screws, mount the Burglary Module to the two HW1490
Support Bars (if not already pre-assembled).
TERMINAL DESCRIPTIONS
Maximum Burglary alarm and standby current can not ex-
ceed calculated maximum available Power Supply Cur-
rent or Available Battery Standby Current, whichever is
less. Typically, this is determined by the Available Bat-
tery Standby Current. Both must be calculated using de-
tailed spreadsheets to be created and provided for review
by the authority having jurisdiction.
Note: There are no integral burglary zones. Burglary
zones require either GEMC-EZM's wired to the Burg Bus,
SLC's connected to the motherboard, or a wireless re-
ceiver (GEMC-RECV) wired to the Fire bus (may be wired
to the Burg bus on a Burg-only system).
BELL ("Bell Output")
Terminal 1: Burg (+)
Terminal 2: Burg (–)
Supervised for open; use only one bell for proper super-
vision. Do not wire to Fire devices. Power limited out-
put.
AUX PWR
Terminal 3: Aux Power (+)
Terminal 4: Aux Power (–)
Separate Burglary Auxiliary Power for Burglary periph-
erals such as PIR's. Power limited output. Do not wire
to Fire devices.
PGM1, 2
Terminal 5, 6: PGM1 (–), PGM2 (–)
Programmable by zone, active low open collector out-
puts. Do not wire to Fire devices.
BURG BUS ("Remote Bus")
Terminal 7: Remote (+)
Terminal 8: Remote (–)
Terminal 9: Remote GRN
Terminal 10: Remote YEL
Do not wire to Fire devices.
Peripherals: GEMC-BK1 (at least one required),
GEMC-EZM, GEMC-OUT8, GEMC-RM3008, GEM-
ACM1D and GEMC-RECV. Separate Burglary Bus
supports all existing Gemini C-Series burglary peripher-
als and a maximum of 15 keypads (using separate
UL603 or UL1481 listed power supply, model GEMC-
12V2APS-CF or GEMC-12V2APS-R).
AUX RELAY
Terminal 11: COM
Terminal 12: N/C
Terminal 13: N/O
JP2 (Burg Service Jumper)
For Combination Fire and Burglary systems. When the
shunt is placed on the two left pins ("ON") of this three-pin
jumper, the system enters a special mode named "Burg
Service Mode" where the system stops processing Bur-
glary (non-Fire) alarm functions to permit the Burglary
part of the system to be serviced (changed) while allow-
ing the Fire system to continue to function as intended.
When servicing the Burglary system, we recommend en-
tering Burg Service Mode before removing power to avoid
the various troubles (such as a Burg keypad trouble) that
will occur. When Burg Service Mode is on, an LED lo-
cated just below the jumper will light. A Burg Service
Mode jumper is also located on the control panel mother-
board that is in parallel with the JP2 jumper on the
GEMC-BM/PS; either jumper can be used to initiate Burg
Service Mode, and the LED located just below the jumper
will light.
JP3 (No Time Out / 4.5 Hour Limit AC Fail Jumper)
The GEMC-BM draws all of its power from the control
panel motherboard. This three-pin jumper allows for the
selection of one of two options if the motherboard loses
AC power:
NO TIME OUT: Place the shunt on the two left pins (or
remove the shunt entirely) for power to be provided to
the GEMC-BM (and its connected devices) from the
motherboard until the battery power supplying the
motherboard is exhausted (and consequently both the
motherboard and the GEMC-BM Burglary module will
no longer be powered). The jumper is placed on these
two right pins ("NO TIME OUT") at the factory.
TIMED LIMIT AC FAIL: Not recommended to be en-
abled for Burglary Only systems. If the motherboard
loses AC power and the shunt is placed on the two right
pins, motherboard battery power will be provided to the
GEMC-BM (and its connected devices) for the pro-
grammed entry in the System Assignment screen
Time Selection tab, the Shed Burg on AC Fail field
(the number entered is x10 minutes). After the selected
time, power to the GEMC-BM will cease, thus conserv-
Item Part Number Description QTY
1 HW1688 Enclosure base 1
2 PCB Burg Burg PCB 1
3 HW1490 Support Bar 2
4 SC628 Thumbscrew 4
5 WA107
#6 External Tooth Star
Washer
4
6 SC270
Screw 6-32 x .25 with
washer (sems)
4